Re: [cobalt-users] Colocation Electric Question
- Subject: Re: [cobalt-users] Colocation Electric Question
- From: "E.B. Dreger" <eddy+public+spam@xxxxxxxxxxxxxxxxx>
- Date: Sat Mar 30 06:07:56 2002
- List-id: Mailing list for users to share thoughts on Cobalt products. <cobalt-users.list.cobalt.com>
> Date: Sat, 30 Mar 2002 12:24:51 -0500
> From: Gerald Waugh <gwaugh@xxxxxxxxxxxxxxxxxxxxxxx>
> 20 * 120 ~ 2400 watts
20A * 120V = 2400VA = ???? Watts
You assumed a power factor of 1.00 -- which is true when voltage
and current are in phase, which is probably not the case.
Watts = VA * pf
> All equipment has a power rating.
> 120 watts is roughly equivalent to 1 amp
> thus 20 amps would power roughly 20 120 watt appliances.
Assuming that the actual current draw is 1A. Chances are that
it's less.
Look at your home breaker box -- chances are that you have a
100A, 150A, or 200A main, but your individual breakers total a
number much higher. Sort of the same idea.
To the OP: Does your colo provide battery backup? If not, you
should probably hook up your own 2400VA UPS... when it complains
about overload, you know that you have too much connected. :-)
Note also that current draw is highest when powering up
equipment.
--
Eddy
Brotsman & Dreger, Inc. - EverQuick Internet Division
Phone: +1 (316) 794-8922 Wichita/(Inter)national
Phone: +1 (785) 865-5885 Lawrence
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~